Model |
HESS-HY-T-08K |
HESS-HY-T-10K |
HESS-HY-T-12K |
| PV Input | |||
| Max. PV array power | 12000Wp | 15000Wp | 18000Wp |
| Max. input voltage | 1100V | ||
| MPP voltage range / rated input voltage | 200 V to 950 V / 630 V | ||
| Min. input voltage / start voltage | 60 V / 180 V | ||
| No. of independent MPP trackers/ strings per MPPT input | 2 /1 | ||
| Max. input current per MPP tracker | 20A | ||
| Max. short-circuit current per MPP tracker | 30A | ||
| Battery Input | |||
| Battery voltage range | 120 V to 600 V | ||
| Max. charging / discharging power | 8000 W | 10000 W | 12000 W |
| Max. charging current /Max. discharging current | 36 A | ||
| Rated charging current /Rated discharging current | 30 A | ||
| Battery type | LiFePO4 | ||
| AC Output | |||
| AC voltage range /Nominal AC voltage | 270 V to 480 V /3/N/PE,220 / 380 V; 230 / 400 V; 240 / 415 V | ||
| Rated AC grid frequency | 50 Hz / 60 Hz | ||
| AC grid frequency range | 45-55 Hz /55-65 Hz | ||
| Rated apparent power | 8000 VA | 10000 VA | 12000 VA |
| Max. apparent power | 8000 VA | 10000 VA | 12000 VA |
| Rated grid output current (@400V) | 11.6 A | 14.5 A | 17.4 A |
| Max. grid output current(@400V) | 12.8 A | 16.0 A | 19.2 A |
| Harmonics THDi (@ Nominal power) | <3% (of nominal power) | ||
| AC Input | |||
| Rated grid voltage | 3/N/PE, 220 / 380 V; 230 / 400 V; 240 / 415 V | ||
| Rated grid frequency | 50 Hz / 60 Hz | ||
| Max. input power from grid | 16000 W | 20000 W | 24000 W |
| Max. input current from grid | 23.2 A | 29.0 A | 34.8 A |
| Efficiency | |
| MPPT efficiency | 99.9 % |
| Euro efficiency / Max. efficiency | 97.9 % / 98.4 % |
| Safety Protection | |
| DC surge protection (Type ll, according to EN/IEC 61643-11) |
. |
| Insulation resistance detection |
. |
| PV string input reverse polarity protection |
. |
| Battery input reverse polarity protection |
. |
| Ground fault monitoring |
. |
| Residual current monitoring unit |
. |
| AC short circuit protection |
. |
| Anti-islanding protection |
. |
| General Data | |
| Power factor at rated power /adjustable displacement | 1 / 0.8 leading to 0.8 lagging |
| Dimensions (W/H/D) | 545 mm / 465 mm / 205 mm |
| Weight | 24.5 kg |
| Operating temperature range | -25℃ …+60℃ |
| Cooling concept | Natural Convection |
| Degree of protection(as per IEC 60529) | IP66 |
| Max. relative humidity | 100 % |
| Max. operating altitude | 4000 m |
| Features | |
| User interface | LED & APP |
| BMS interface | CAN |
| Smart meter interface | RS485 |
| Internet communication interfaces | WiFi / LAN / 4G / Bluetooth |
| Digital output (dry contact) / No. of outputs |
. / 2 |
| Digital input (dry contact) / No. of inputs | . / 4 |
| Integrated power control / export power control |
. / . |
| Nominal output voltage | 3/N/PE, 220 / 380 V; 230 / 400 V; 240 / 415 V | ||
| Nominal output frequency | 50 Hz / 60 Hz | ||
| Rated apparent power | 8000 VA | 10000 VA | 12000 VA |
| Peak output apparent power | 2 times of rated power, 10 s | ||
| Rated current (@400V) | 11.6 A | 14.5A | 17.4 A |
| Max. switch time | <10 ms | ||
| Output THDv(@ Linear load) | 2% | ||







Reviews